TELEMECANIQUE XS212BLPAL2 — Non-Flush Cylindrical Inductive Sensors

Telemecanique XS212BLPAL2: Inductive proximity sensor, M12, non-flush, Sn 4 mm, PNP 1 NO, 2 m cable, 12–24 V DC.

Telemecanique XS212BLPAL2 — Inductive proximity sensor, M12, non-flush

Status: In production

Brand: Telemecanique

Product: Inductive proximity sensor, M12, non-flush

Sensing distance (Sn): 4 mm

Output: PNP, 1 NO

Connection: 2 m cable

Supply: 12–24 V DC

Degree of protection: IP67

Request a quote for price and stock

The Telemecanique XS212BLPAL2 is an XS2-family inductive proximity sensor of the XS range with a cylindrical M12 x 1 threaded body. It is non-flush mountable; in a metal support the data sheet requires d ≥ 36 mm and h ≥ 8 mm. Nominal sensing distance (Sn) is 4 mm, with an operating zone of 0–3.2 mm. Enclosure is nickel-plated brass, sensing face PBT; length 44 mm, threaded length 26 mm, net weight 0.07 kg. Differential travel is 1–15 % of the effective sensing distance; switching frequency is up to 1200 Hz.

Supply is 12–24 V DC (limits 10–36 V DC) with reverse polarity protection. The PNP 1 NO output switches up to 200 mA with overload and short-circuit protection; closed-state voltage drop is below 2 V and no-load current consumption is at most 10 mA. Connection is via a 2 m PVC-insulated 3 x 0.14 mm² cable; a yellow LED shows the output state. Degree of protection is IP67 (IEC 60529); operating temperature is -25 to +70 °C. Certifications: UL and CSA.

Telemecanique XS212BLPAL2 technical specifications

General
SeriesXS2, general purpose
Body designCylindrical, M12 x 1 thread
MountingNon-flush mountable
Detection
Nominal sensing distance (Sn)4 mm
Operating zone (Sa)0–3.2 mm
Differential travel1–15 % of effective sensing distance (Sr)
Switching frequency≤ 1200 Hz
Electrical characteristics
Rated supply voltage12–24 V DC with reverse polarity protection
Supply voltage limits10–36 V DC
Current consumption (no-load)≤ 10 mA
Voltage drop (closed state)Below 2 V
Delays (maximum)First-up 15 ms; response 0.15 ms; recovery 0.4 ms
Outputs and indicators
Output typePNP, 1 NO, DC
Wiring technique3-wire
Switching capacity≤ 200 mA with overload and short-circuit protection
Status LEDOutput state: 1 yellow LED
Mechanical and connection
Electrical connection2 m cable
Cable3 x 0.14 mm², PVC insulation
Enclosure materialnickel-plated brass
Sensing face materialPBT
Length / threaded length44 mm / 26 mm
Net weight0.07 kg
Minimum mounting distancesSide by side ≥ 16 mm; face to face ≥ 48 mm; facing a metal object ≥ 12 mm; mounted in a metal support d ≥ 36 mm, h ≥ 8 mm
Environmental
Degree of protectionIP67 (IEC 60529)
Operating temperature-25 to +70 °C
Storage temperature-40 to +85 °C
Vibration resistance25 gn, amplitude ±2 mm (f = 10–55 Hz), IEC 60068-2-6
Shock resistance50 gn for 11 ms, IEC 60068-2-27
Marking and certificationsCE; UL, CSA

Key features

  • Sn 4 mm, non-flush mountable, M12 x 1 thread
  • PNP 1 NO output, up to 200 mA, overload and short-circuit protected
  • 12–24 V DC supply with reverse polarity protection
  • Nickel-plated brass enclosure, PBT sensing face
  • Degree of protection IP67
  • 2 m PVC cable, yellow status LED

XS212BLPAL2 ordering codes

Part numberDescription
XS212BLPAL2PNP, 1 NO, 2 m cable
XS212BLPAM12PNP, 1 NO, M12 connector
XS212BLNAL2NPN, 1 NO, 2 m cable
XS212BLNAM12NPN, 1 NO, M12 connector
XS212BLPBL2PNP, 1 NC, 2 m cable
XS212BLNBL2NPN, 1 NC, 2 m cable

XS212BLPAL2 accessories

Accessories listed by the manufacturer for this product (ordered separately):

Part numberDescription
XSZB112Fixing clamp for Ø12 mm XS inductive sensors, plastic, with indexing
XSZBS12Mounting bracket for Ø12 mm XS inductive sensors, stainless steel

Other Telemecanique Non-Flush Cylindrical Inductive Sensors

Models from other brands: Non-Flush Cylindrical Inductive Sensors

Is this inductive sensor right for your application?

Share the metal target to be detected (material, size), the required sensing distance, the mounting type (flush / non-flush), ambient conditions (oil, coolant, washdown, temperature) and your PLC input (PNP/NPN, NO/NC); let’s select the right inductive sensor and connection cable together.

Request a quote Back to Non-Flush Cylindrical Inductive Sensors

All product specifications are subject to change without notice. Source: Telemecanique Sensors, XS212BLPAL2 product data sheet (https://downloads.telemecaniquesensors.com/dam/datasheets/en/XS212BLPAL2_EN.pdf, 30 July 2024); reference page https://www.telemecaniquesensors.com/global/en/product/reference/XS212BLPAL2; XS catalogue TESEBRO000040EN (accessed 28 September 2026).