← RS-485 I/O Modules: ADAM-4000/4100
ADAM-4018+

ADAM-4018+

8Thermocouple Modbus RS-485 Remote I/O
Key Features
  • 8ch thermocouple(can be set to current)
  • Protocols:Modbus RTU,ASCII
  • Watchdog timer to recover the system
  • 3000VDC isolation protection
  • Wiring burned-out detection function
Detailed Specifications
Analog Input — Burn-out DetectionYes
Communications — InterfaceRS-485
Environment — Isolation Voltage3,000 VDC
Environment — Operating Temperature-10~70 °C (14~158 °F)
General — Connectors2 x 10-pin plug-in screw terminal
General — ProtocolASCII command, Modbus/RTU
Power Requirements — Input Voltage10~30 VDC
Thermocouple Input — Channels8
Thermocouple Input — Input TypemA, T/C: J, K, T, E, R, S, B type
Thermocouple Input — Resolution16-bit
Thermocouple Input — Sample Range10 S/s (sum)
Thermocouple Input — Temperature RangeType J (0~760° C), Type K (0~1370° C), Type T (-100~400° C), Type E (0~1000° C), Type R (500~1750° C), Type S (500~1750° C), Type B (500~1800° C)
Thermocouple Input — Voltage Range±20 mA, 4~20 mA
Hardware — CertificationCE, FCC