← IoT Ethernet I/O Modules: ADAM-6000/6200
ADAM-6018+

ADAM-6018+

8Thermocouple IoT Modbus/SNMP/MQTT Ethernet Remote I/O
Key Features
  • 8ch thermocouple
  • Protocols:MQTT(TLS),SNMP,Modbus TCP,RESTful API,ASCII
  • GCL to perform basic logic control rules
  • Peer-to-Peer function to map I/O status
  • Watchdog timer to recover the system
  • Built-in web server
Detailed Specifications
Communications — InterfaceEthernet
Environment — Isolation Voltage2,000 VDC
Environment — Operating Temperature-40~70 °C (-40~158 °F)
General — Connectors1 x RJ45, 1 x 13-pin plug-in screw terminal, 1 x 9-pin plug-in screw terminal
General — ProtocolModbus/TCP, TCP/IP, UDP, HTTP, DHCP, MQTT, SNMP, ASCII command
Power Requirements — Input Voltage10~30 VDC
Thermocouple Input — Channels8
Thermocouple Input — Sample Range10 S/s (sum)
Thermocouple Input — Temperature RangeType J (0~760° C), Type K (0~1370° C), Type T (-100~400° C), Type E (0~1000° C), Type R (500~1750° C), Type S (500~1750° C), Type B (500~1800° C)