← RS-485 I/O Modules: ADAM-4000/4100

ADAM-4019+
8Thermocouple Modbus RS-485 Remote I/O
Key Features
- 8ch thermocouple(can be set to voltage or current)
- Protocols:Modbus RTU,ASCII
- Watchdog timer to recover the system
- 3000VDC isolation protection
- Wiring burned-out detection function
Detailed Specifications
| Analog Input — Burn-out Detection | Yes |
| Communications — Interface | RS-485 |
| Environment — Isolation Voltage | 3,000 VDC |
| Environment — Operating Temperature | -10~70 °C (14~158 °F) |
| General — Connectors | 2 x 10-pin plug-in screw terminal |
| General — Protocol | ASCII command, Modbus/RTU |
| Power Requirements — Input Voltage | 10~30 VDC |
| Thermocouple Input — Channels | 8 |
| Thermocouple Input — Input Type | mA, mV, V, T/C: J, K, T, E, R, S, B, N type |
| Thermocouple Input — Resolution | 16-bit |
| Thermocouple Input — Sample Range | 10 S/s (sum) |
| Thermocouple Input — Temperature Range | Type J (0~760° C), Type K (0~1370° C), Type T (-100~400° C), Type E (0~1000° C), Type R (500~1750° C), Type S (500~1750° C), Type B (500~1800° C), Type N (-200~1300° C) |
| Hardware — Certification | CE, FCC |
| Analog Input — Input Range | ±100 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, ±10 V, 0~20mA, 4 ~ 20 mA, ±20 mA, 0~100 mV, 0~500 mV, 0~1 V, 0~2.5 V, 0~5 V, 0~10 V |